Setting Up Auto-Shutdown for a Prolink PRO851SFCU UPS on Debian

I recently picked up a Prolink PRO851SFCU UPS to protect my home server setup against unexpected power trips. Getting the hardware plugged in is only half the battle — the real work is configuring Network UPS Tools (NUT) to handle a graceful, automated shutdown before the battery drains completely.

Here is the complete configuration blueprint for setting up NUT with a 2-minute timed auto-shutdown on Debian.

Step 1: Hardware & Package Installation

Connect the UPS to the server via the USB-A to USB-B cable, then install the NUT packages:

bash
sudo apt update && sudo apt install nut nut-client nut-server

Step 2: Driver & Monitoring Configuration

Because the Prolink PRO851SFCU uses a single 12V 10Ah battery and a Voltronic-QS USB chip, we override the low/high voltage limits in /etc/nut/ups.conf to get an accurate 0–100% state-of-charge calculation and prevent poll disconnect spam:

ini
# /etc/nut/ups.conf
[prolink]
    driver = nutdrv_qx
    port = auto
    desc = "Prolink PRO851SFCU"
    override.battery.voltage.low = 9.6
    override.battery.voltage.high = 13.2
    override.battery.packs = 1
    pollinterval = 2

Set the operation mode to standalone in /etc/nut/nut.conf:

ini
# /etc/nut/nut.conf
MODE=standalone

Define local monitoring credentials in /etc/nut/upsd.users:

ini
# /etc/nut/upsd.users
[monuser]
    password = secretpass
    upsmon primary

Configure upsmon in /etc/nut/upsmon.conf to delegate events to upssched:

ini
# /etc/nut/upsmon.conf
MONITOR prolink@localhost 1 monuser secretpass primary
SHUTDOWNCMD "/sbin/shutdown -h now"
POWERDOWNFLAG /etc/killpower

NOTIFYCMD /sbin/upssched
NOTIFYFLAG ONLINE   EXEC+WARN+REGARD
NOTIFYFLAG ONBATT   EXEC+WARN+REGARD
NOTIFYFLAG LOWBATT  EXEC+WARN+REGARD

Step 3: Timed Shutdown Script

To prevent the server from instantly shutting down during brief brownouts, set up a 120-second timer buffer in /etc/nut/upssched.conf:

ini
# /etc/nut/upssched.conf
CMDSCRIPT /etc/nut/upssched-cmd
PIPEFN /var/run/nut/upssched.pipe
LOCKFN /var/run/nut/upssched.lock

AT ONBATT * START-TIMER shutdown_timer 120
AT ONLINE * CANCEL-TIMER shutdown_timer

Create the execution script at /etc/nut/upssched-cmd (ensure the double 's' in upssched to avoid execution errors):

bash
#!/bin/sh
case $1 in
    shutdown_timer)
        /sbin/shutdown -h now "UPS on battery for 2 minutes. Shutting down system."
        ;;
    *)
        logger -t upssched-cmd "Unknown event: $1"
        ;;
esac

Apply execution permissions and set ownership for the nut user:

bash
sudo chmod +x /etc/nut/upssched-cmd
sudo chown nut:nut /etc/nut/upssched-cmd

Step 4: Verification & Service Startup

Clear any stuck PID files, enable the systemd services, and test the connection:

bash
sudo systemctl stop nut-server nut-client
sudo rm -f /run/nut/*.pid
sudo systemctl restart nut-server nut-client
sudo systemctl enable nut-server nut-client

Running upsc prolink@localhost should now report ups.status: OL and battery.charge: 100. You can safely test the script logic by manually executing sudo /etc/nut/upssched-cmd shutdown_timer and cancelling it with sudo shutdown -c.