I recently picked up a Prolink PRO851SFCU UPS to protect my home server setup against unexpected power trips. Getting the hardware plugged in is only half the battle — the real work is configuring Network UPS Tools (NUT) to handle a graceful, automated shutdown before the battery drains completely.
Here is the complete configuration blueprint for setting up NUT with a 2-minute timed auto-shutdown on Debian.
Step 1: Hardware & Package Installation
Connect the UPS to the server via the USB-A to USB-B cable, then install the NUT packages:
sudo apt update && sudo apt install nut nut-client nut-server
Step 2: Driver & Monitoring Configuration
Because the Prolink PRO851SFCU uses a single 12V 10Ah battery and a Voltronic-QS USB chip, we override the low/high voltage limits in /etc/nut/ups.conf to get an accurate 0–100% state-of-charge calculation and prevent poll disconnect spam:
# /etc/nut/ups.conf
[prolink]
driver = nutdrv_qx
port = auto
desc = "Prolink PRO851SFCU"
override.battery.voltage.low = 9.6
override.battery.voltage.high = 13.2
override.battery.packs = 1
pollinterval = 2
Set the operation mode to standalone in /etc/nut/nut.conf:
# /etc/nut/nut.conf
MODE=standalone
Define local monitoring credentials in /etc/nut/upsd.users:
# /etc/nut/upsd.users
[monuser]
password = secretpass
upsmon primary
Configure upsmon in /etc/nut/upsmon.conf to delegate events to upssched:
# /etc/nut/upsmon.conf
MONITOR prolink@localhost 1 monuser secretpass primary
SHUTDOWNCMD "/sbin/shutdown -h now"
POWERDOWNFLAG /etc/killpower
NOTIFYCMD /sbin/upssched
NOTIFYFLAG ONLINE EXEC+WARN+REGARD
NOTIFYFLAG ONBATT EXEC+WARN+REGARD
NOTIFYFLAG LOWBATT EXEC+WARN+REGARD
Step 3: Timed Shutdown Script
To prevent the server from instantly shutting down during brief brownouts, set up a 120-second timer buffer in /etc/nut/upssched.conf:
# /etc/nut/upssched.conf
CMDSCRIPT /etc/nut/upssched-cmd
PIPEFN /var/run/nut/upssched.pipe
LOCKFN /var/run/nut/upssched.lock
AT ONBATT * START-TIMER shutdown_timer 120
AT ONLINE * CANCEL-TIMER shutdown_timer
Create the execution script at /etc/nut/upssched-cmd (ensure the double 's' in upssched to avoid execution errors):
#!/bin/sh
case $1 in
shutdown_timer)
/sbin/shutdown -h now "UPS on battery for 2 minutes. Shutting down system."
;;
*)
logger -t upssched-cmd "Unknown event: $1"
;;
esac
Apply execution permissions and set ownership for the nut user:
sudo chmod +x /etc/nut/upssched-cmd
sudo chown nut:nut /etc/nut/upssched-cmd
Step 4: Verification & Service Startup
Clear any stuck PID files, enable the systemd services, and test the connection:
sudo systemctl stop nut-server nut-client
sudo rm -f /run/nut/*.pid
sudo systemctl restart nut-server nut-client
sudo systemctl enable nut-server nut-client
Running upsc prolink@localhost should now report ups.status: OL and battery.charge: 100. You can safely test the script logic by manually executing sudo /etc/nut/upssched-cmd shutdown_timer and cancelling it with sudo shutdown -c.